The SpeedStile BP DS requires two types of cables:
Power supply cables
Signal transmission cables
All cables and conduits are to be supplied by client and installed prior to installation. Gunnebo
provides the interconnection 230VAC cable and the CAN bus cable.
For units that are to be controlled by Card Access or similar it is recommended that Gunnebo
Entrance Control Technical Personnel are advised prior to starting the installation routines.
The following instructions should be followed when laying cables:
-
The incoming mains power cables should be routed to the MASTER end.
-
The earth conduit for the CAN bus cable shall not overcome 3 m of length.
-
Earth conduits with a diameter no less than 20 mm.
-
Lay the conduits for the power cables and those for data trans-mission cables
separately.
-
Lay the conduits away from high voltage cables or cables with radio-frequencies,
electric motors and other machines.
-
Place the conduits as far as possible from the barrier's anchor holes in the floor.
-
Conduits must be directed towards the position for the cables on the barrier (see
the layout shown in this section). The conduits must rise at least 50 mm from the
foundation base.
-
Cables must rise from the floor with a length that reaches the logic panel on the
barrier top or to the integrated reader mounted on the barriers (at least 1.5 m).
Taken care when running the cables because curves with tight radii can damage
the cables.
-
Use cable grommets to protect from abrasive edges and cable-ties or similar in
order to prevent cables wrenching.