ADV200 WA • Quick start up guide - Specification and installation
5.2.5 Power supply unit regulation card (only for sizes ≥ 72000)
Figure 1: Terminals location
Terminals
Function
Voltage / Current
23
Input of the precharge enable control
(15 - 35V, 5 - 11mA)
32
Output of the MLP static signal (low - active signal)
(5 … 35V, 20mA source)
33
(Common) Ground of the MLP and ML static signals
-
34
Reference point for Power 24V
-
35
Power supply 24V
(32V / 300mA max)
36
Output of the ML signal (low - active signal)
(5 … 35V, 20mA max sink)
37
Power supply of the ML and MLP signals
(35V max)
52
(Common) Ground of the precharge enable control
-
70, 72
OK Relay
(max 250VAC, 1A – AC11)
Note!
The jumpers shown are factory-wired.
Wiring of the OK relay contact (70 - 72) in series with the Enable chain of the ADV200 WA regulation
card is recommended.
Dip-switch and Jumper
S6 - S7
Selection of the AC mains frequency: 50 or 60 Hz