96
ADV200 WA • Quick start up guide - Specification and installation
Index Error message shown
on the display
Sub-code
Description
Solution:
Ask Gefran for the correct key to enable the desired firmware function.
20
Param error
Condition
: if an error occurs during activation of the parameter database saved in flash; the alarm
is inserted in the alarm list and alarm log.
XXX0H-X
The code XXXXH-X indicates the IPA of the parameter that has been set outside the
range allowed when the database is enabled.
Solution
: Set the parameter causing the error to a value within the range and run
Save param-
eters
. Switch the drive off and then switch it back on again.
If the IPA of the parameter is not shown in the manual, contact the service centre.
21
22
Options cfg changed
Condition
: this may occur when powering the drive if an expansion card has been removed or
replaced or the incorrect enable key is inserted for a given firmware function.
0064H-100
Card removed from slot 1
0014H-20
Card removed from slot 2
0003H-3
Card removed from slot 3
0078H-120
Card removed from slot 1 and from slot 2
0067H-103
Card removed from slot 1 and from slot 3
0017H-23
Card removed from slot 2 and from slot 3
007BH-123
Card removed from slot 1, from slot 2 and from slot 3
Solution
: Check the hardware configuration, then press ESC. Save the parameters (
Save param-
eters
, menu 04.01 par 550) to save the new hardware configuration.
Note!
If any messages not included in this list are displayed, reference should be made to the manual of the
application used by the drive.