44
ADV200 WA • Quick start up guide - Specification and installation
Table 5.2.3.1: Regulation terminals
Strip T2 (top)
Terminal
Designation
Function
Max
R21
COM Digital
output 2
Common reference for digital output 2 (Relay 2)
-
R24
Digital output 2
Programmable digital relay output 2 (NO). Default =
Drive ready
250 V
ac
- 30 V
dc
/ 2A
5
Analog output 1
Analog output 1. Default =
Null (not assigned)
±12,5 V (typical ±10 V / 5 mA)
6
Analog output 2
Analog output 2. Default =
Null (not assigned)
- voltage (default):
±12,5 V (typical ±10V/5mA)
- current (set by S3 switch):
0...20mA or 4...20mA (setting by
PAR 1848, 15 - ANALOG OUPUTS
menu)
C1
COM Analog output
Common reference for analog outputs and ±10V potential voltage reference
-
7
Digital input E
Digital input E . Default =
Digital input E mon (Enable)
5mA @ +24V (+30V max)
8
Digital input 1
Digital input 1 . Default =
FR forward src, PAR 1042
5mA @ +24V (+30V max)
9
Digital input 2
Digital input 2 . Default =
FR reverse src, PAR 1044
5mA @ +24V (+30V max)
10
Digital input 3
Digital input 3 . Default =
Multi ref sel 0 src
5mA @ +24V (+30V max)
11
Digital input 4
Digital input 4 . Default =
Multi ref sel 1 src
5mA @ +24V (+30V max)
12
Digital input 5
Digital input 5 . Default =
Fault reset src
5mA @ +24V (+30V max)
C2
COM Digital inputs
Common reference for digital inputs
-
C3
0V 24 OUT
Reference point for +24V OUT
-
S3
+ 24V OUT
+24V supply for IO
150 mA
(Resettable fuse)
, ±10 %
Strip T1 (bottom)
Terminal
Designation
Function
Max
R11
COM Digital
output 1
Common reference for digital output 1 (Relay 1)
-
R14
Digital output 1
Programmable digital relay output 1 (NO). Default =
Drive OK
250 V
ac
- 30 V
dc
/ 2A
1
Analog input 1
Programmable / configurable analog differential input.
Signal: terminal 1. Reference: terminal 2.
Default =
Multi ref 0 src
- voltage (default):
±12,5 V (typical ±10V/1mA)
- current (set by switches S1-S2):
0...20mA or 4...20mA (set by
PAR 1502 or 1552, 14 - ANALOG
INPUTS menu)
2
3
Analog input 2
Programmable / configurable analog differential input.
Signal: terminal 3. Reference: terminal 4.
Default =
Not used
4
S1+
+10 V
Voltage ref10V; reference point: C1 terminal
+10 V ±1% / 10 mA
S1-
- 10V
Analog output -10V; reference point: C1 terminal
-10 V ±1% / 10 mA
13
Digital output 3
Digital output 3. Default =
Speed is 0 delay
+24 V /
20 mA (typ), 40 mA (max)
14
Digital output 4
Digital output 4. Default =
Ref is 0 delay
+24 V /
20 mA (typ), 40 mA (max)
IS1
PS Digital output
Digital outputs 3 / 4 power supply
-
IC1
COM Digital output
Common reference for digital outputs 3 / 4
-
IC2
0V 24 EXT
Reference for regulation card 24V external supply
-
IS2
+ 24V EXT
External supply of regulation card
+24V ±10% / 1A