52
ADV200 WA • Quick start up guide - Specification and installation
5.4 Serial interface (XS connector)
XS
Function
I/O
Electr. interface
PIN 1
Internal use
–
–
PIN 2
Internal use
–
–
PIN 3
RxA/TxA
I/O
RS485
PIN 4
Equipotentiality (optional)
–
–
PIN 5
0V (Ground for 5 V)
–
Power supply
PIN 6
Internal use
–
–
PIN 7
RxB/TxB
I/O
RS 485
PIN 8
Internal use
–
–
PIN 9
+5 V
–
Power supply
I = Input
O = Output
The ADV200 WA drive is equipped as standard with a port (9-pin D-SUB recep-
tacle connector:
XS
) for connection of the RS485 serial line used for drive/PC
point-to-point communication (through the GF-eXpress configuration software) or
for multi-drop connection.
To access the connector, remove the lower cover as illustrated in shown in
para-
graph 5.2.1
.
5.4.1 Drive / RS 485 Port (not insulated) point-to-point connection
The connection indicated is without galvanic insulation !
Le raccordement indiqué n’a pas d’isolation galvanique !
1
2
3
4
5
9
8
7
6
TxA/RxA
TxB/RxB
PE
+5 V
XS
Reserved
RS485
EQP
Figure 5.4.1.1: Serial connection (not insulated)
A twin-pair consisting of two symmetrical conductors, spiral wound with a common
shield plus the bonding connection cable, connected as shown in the figure, must
be used for connection. The transmission speed is 38.4 kBaud.
For connection of the RS485 serial line to the PC, see the figure below.
Caution