ADV200 WA • Quick start up guide - Specification and installation
• Jog
Finally, for Jog mode, select the control terminal in the
Jog cmd + src
parameter
(09 - JOG FUNCTION menu, PAR: 916), using a signal from selection list L_DIG-
SEL2.
The Jog speed must be written in the
Jog setpoint
parameter (PAR: 910), while
the acceleration and deceleration ramps can be set, respectively, in
Jog accelera-
tion
(PAR: 912) and
Jog deceleration
parameters (PAR: 914).
• Speed limits
After selecting the reference, set the speed limits in the following parameters (05 -
REFERENCES menu):
-
Full scale speed
(PAR: 680). Setting of the maximum motor speed, which
usually coincides with the rated speed indicated on the motor data plate.
-
Speed ref top lim
(PAR: 670). Upper speed limit: the maximum setting is
200% of the
Full scale speed
.
-
Speed ref bottom lim
(PAR: 672). Lower speed limit: the maximum setting is
-200% of the
Full scale speed
.
-
Overspeed threshold
(24 - ALARM CONFIG menu, PAR: 4540). Overspeed
alarm limit.
• Input and Output terminals
The default setting of the input terminals is as follows:
- Terminal 7
Digital input E
Enable
- Terminal 8
Digital input 1
FR forward src, PAR 1042
- Terminal 9
Digital input 2
FR reverse src, PAR 1044
- Terminal 10
Digital input 3
Multi ref sel 0 src
- Terminal 11
Digital input 4
Multi ref sel 1 src
- Terminal 12
Digital input 5
Fault reset src
- Terminal S3
+ 24V OUT
I/O supply
The default configuration of the terminals dedicated to digital outputs are as fol-
lows:
- Terminal R14
Digital output 1
Drive OK (Relay 1)
- Terminal R11
COM Digital output 1
Common digital output 1 (Relay 1)
- Terminal R24
Digital output 2
Drive ready (Relay 2)
- Terminal R21
COM Digital output 2
Common digital output 2 (Relay 2)
- Terminal 13
Digital output 3
Speed is 0 delay
- Terminal IC1
COM Digital output 3/4
Common ref. for digital outputs 3 / 4
- Terminal 14
Digital output 4
Ref is 0 delay
- Terminal IS1
PS Digital output 3/4
Digital outputs 3 / 4 power supply
Signals for the digital outputs can be programmed using the
Digital output 1...4
src
parameters (13 - DIGITAL OUTPUTS menu, PAR: from 1310 to 1316) using
the settings in the L_DIGSEL1 selection list.
The drive also includes two analog outputs which are not factory-set. These
outputs must be enabled by setting
Analog out 1 src
(15 - ANALOG OUTPUTS
menu, PAR: 1800) and
Analog out 2 src
parameters (PAR: 1802) with a signal
selected from selection list L_ANOUT.
The signal available on analog output 1 is ± 10V, while the analog output 2 signal
can be selected using the
Analog out 2 type
parameter (PAR: 1848) between:
0
0-20mA
1
4-20mA
2
± 10V