106
ADV200 WA • Quick start up guide - Specification and installation
9.7 Voltage level of the inverter for safe operations
The minimum time
between the moment in which an ADV200 WA drive is disa-
bled from the mains and that in which an operator can operate on internal parts of
the drive, without the danger of electric shock
, is 5 minutes.
The value consider the time to turn-off for a drive supplied at 460V
ac
+10%, without any
options (time indicated for disabled drive condition).
Attention