36
ADV200 WA • Quick start up guide - Specification and installation
1000 ... 1200 kW (ADV200 WA-...-DC)
C
D
U
V
W
ADV-...-MS..-4-DC
C
D
U
V
W
ADV-...-SL-4-DC
(450 ... 750 V
)
DC
K1M
F1
F1
C
D
U
V
W
ADV-...-SL-4-DC
F1
Note!
Terminals BR1/BR2 are standard up to size ADV200 WA-3300, optional in sizes ADV200 WA-4370 ...
5750, larger sizes are not used.
Recommended combination F1 fuses: see
paragraph
“10.1 Optional external fuses”, page 117
.
5.1.7 Input mains choke (L1)
Sizes ADV200 WA-1015 ... 61600:
Integrated on DC-link.
Sizes ADV200 WA-72000 ... and above
: external choke mandatory (for the rec-
ommended combination see chapter
“10.2.1 Optional input chokes (L1)”, page 120
.
Sizes ADV-...-DC: not available
.