94
ADV200 WA • Quick start up guide - Specification and installation
Index Error message shown
on the display
Sub-code
Description
6
Power config
Condition:
may occur during recognition of power cards. If this message is displayed, it is not
possible to drive the motor.
0020H-32
The power card is configured for a drive that is incompatible with the regulation
card
0021H-33
The configuration of the power card is not compatible with the regulation card
0017H-23
The configuration required is not available on the power card
Solution:
Download the correct configuration on the power card
7
Save par failed
Condition:
during transfer of the parameters from the drive to the memory of the keypad
0H-0
Communication error
0025H-37
The data saved on the keypad are not valid
0026H-38
Incompatible drive series
0027H-39
Incompatible software version
0028H-40
Incompatible drive size
0029H-41
Error during saving of parameters on the drive
Solution:
8
Load par failed
Condition:
during transfer of the parameters from the memory of the keypad to the drive
9
Load par incomplete
0H-0
Communication error
0025H-37
The data saved on the keypad are not valid.
No parameter is transferred from the keypad to the drive
0026H-38
Incompatible drive series.
No parameter is transferred from the keypad to the drive
0027H-39
Incompatible software version.
All the parameters present in the memory of the keypad have been transferred
to the drive. The set of parameters transferred refers to a drive with a different
firmware version; therefore, certain parameters may not be updated.
0028H-40
Incompatible drive size.
All the parameters present in the memory of the keypad (excluding those that
depend on the size of the drive), have been transferred to the drive. The parameters
that depend on size maintain their original value.
0029H-41
Error during saving of parameters on the drive.
All the parameters present in the memory of the keypad have been transferred to
the drive. The transfer of one or more parameters has caused an “out of range”
error, or one or more parameters does not exist. At the end of transfer, one or more
parameters may not have been updated.
002AH-42
PLC application release and version not compatible.
All parameters in the keypad memory have been transferred to the drive.
The transferred set of parameters relates to a drive with a PLC application in which
the version and release of the application are different. As a result some of the PLC
application parameters may not be updated.
002BH-43
PLC application not compatible.
All the parameters in the keypad memory except those relating to the PLC applcia-
tion have been transferred to the drive.
The transferred set of parameters relates to a drive with a different PLC application.
As a result none of the PLC application parameters are updated.
Solution:
Recover a set of parameters from a compatible drive (model and size)
10
Options config error
Condition:
may occur at drive start-up, during recognition of the optional cards installed
0001H-1
Non-permissible optional card in slot 1
0002H-2
Non-permissible optional card in slot 2
0004H-4
Non-permissible optional card in slot 3
0010H-16
Conflict slot 1 with slot 2
0020H-32
Conflict slot 1 with slot 3