92
ADV200 WA • Quick start up guide - Specification and installation
8.2 Messages
Note !
For more information see
chapter 6.7
.
Index Error message shown
on the display
Sub-code
Description
1
Load default param
Condition:
may occur during loading of the parameter database saved in flash
normally appears in the following conditions: at initial power-on when a new firmware version is
downloaded, when the regulation is installed on a new size, when the region is changed.
If this message is displayed when the drive is already operating, this means that a problem has
occurred in the parameter database saved in Flash.
If this message is displayed the drive restores the default database, i.e. the one downloaded.
0001H-1
The database saved is not valid
0002H-2
The database saved is not compatible
0003H-3
The database saved refers to a different size from the current size
0004H-4
The database saved refers to a different region from the current region
Solution:
Set the parameters to the value required and perform
Save parameter
2
3
4
Option detect slot 1
Option detect slot 2
Option detect slot 3
Condition:
at power-on, the drive recognizes the presence of an optional card in one of the three
expansion slots.
One of the three messages is shown on the display
0H-0
None
0004H-4
Can/DeviceNet
00FFH-255
Unknown
0104H-260
Profibus
0204H-516
Rte
0301H-769
I�O�1
0701H-1793
I�O�2
0901H-2305
I�O�3
0D01H-3329
I�O�4
1601H-5633
I�O�6 (EXP-IO-SENS-100-ADV)
1901H-6401
I�O�7 (EXP-IO-D5R8-ADV)
1E01H-7681
I�O�8 (EXP-IO-SENS-1000-ADV)
Solution:
5
Autotune
Condition:
this may occur during the
Autotune
procedure
0
No error
1
The commands are not configured in Local mode.
Solution
: Execute the requested configuration
2
The Commands local sel parameter has not been configured from the keypad
Solution
: Execute the requested configuration
3
The motor plate data parameters have changed but the
Take parameters
com-
mand, PAR 2020, has not been executed
Solution
: Execute the
Take parameters
command.