Installation
Proline Promag 53 PROFIBUS DP/PA
20
Hauser
3.2.4
Inlet and outlet runs
If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc.
Compliance with the following requirements for the inlet and outlet runs is necessary in order to
ensure measuring accuracy.
• Inlet run:
≥
5 x DN
• Outlet run:
≥
2 x DN
a0003210
Fig. 13:
Inlet and outlet runs
3.2.5
Vibrations
Support and secure the both piping and the sensor if vibration is severe.
"
Caution!
It is advisable to install sensor and transmitter separately if vibration is excessively severe.
Information about the permitted shock and vibration resistance
a0003208
Fig. 14:
Measures to prevent vibration of the measuring device
5 x DN
2 x DN
> 10 m