Commissioning
Proline Promag 53 PROFIBUS DP/PA
118
Hauser
6.6.4
Configuration examples with Simatic S7 HW-Konfig
Example 1
a0004787
Fig. 63:
Complete configuration using the Promag 53 GSD file (complete device functionality)
It is essential to adhere to the following sequence when configuring the modules in the PROFIBUS
master (Class 1):
Slot
sequence
Module
Byte length
input data
Byte length
output data
Description
1
AI
5
-
Analog Input function block 1
Output variable
→
volume flow (factory setting)
2
SETTOT_MODETOT_TOTAL
5
2
Totalizer function block 1
TOTAL
→
output variable = volume flow (factory setting)
SETTOT
→
totalizer control
MODETOT
→
totalizer configuration
3
SETTOT_MODETOT_TOTAL
5
2
Totalizer function block 2
TOTAL
→
output variable = volume flow (factory setting)
SETTOT
→
totalizer control
MODETOT
→
totalizer configuration
4
SETTOT_MODETOT_TOTAL
5
2
Totalizer function block 3
TOTAL
→
output variable = volume flow (factory setting)
SETTOT
→
totalizer control
MODETOT
→
totalizer configuration
5
AI
5
-
Analog Input function block 2
Output variable
→
mass flow (factory setting)
6
DISPLAY_VALUE
-
5
Value for local display
7
CONTROL_BLOCK
-
1
Control of device functions
8
BATCHING_QUANTITY
-
5
Batching quantity
9
BATCHING_FIX_COMP_QUANTITY
-
5
Fixed correction quantity