Wiring
Proline Promag 53 PROFIBUS DP/PA
60
Hauser
4.3.3
PROFIBUS DP connection diagram
Permanent assignment board (order version 53***-***********J)
a0002308
Fig. 34:
Connecting the transmitter, cable cross-section: max. 2.5 mm
2
A
View A (field housing)
B
View B (stainless steel field housing)
C
View C (wall-mount housing)
a
Connection compartment cover
b
Cable for power supply: 85 to 260 V AC, 20 to 55 V AC,16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L- for DC
c
Ground terminal for protective conductor
d
Fieldbus cable
Terminal No. 26: B (RxD/TxD-P)
Terminal No. 27: A (RxD/TxD-N)
e
Ground terminal for fieldbus cable shield
Observe the following:
– the shielding and grounding of the fieldbus cable
– that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible
f
Service adapter for connecting service interface FXA 193 (Fieldcheck, ToF Tool - Fieldtool Package)
g
Cable for external termination:
Terminal No. 24: +5 V
Terminal No. 25: DGND
C
a
d
b
g
a
A
B
d
g
b
d
g
b
27
25
23
21
2
1
26
24
22
20
L1 (L+)
N (L-)
B (
)
RxD/TxD-P
A (RxD/TxD-N)
d
c
e
b
g
f
(DGND)
(+5 V)
1
2
c
e
f
b
d
22 23
20 21
24 25 26 27
(DGND)
(+5 V)
g
L1 (L+)
N (L–)
A (RxD/TxD-N)
B (
)
RxD/TxD-P