Troubleshooting
Proline Promag 53 PROFIBUS DP/PA
144
Hauser
No. # 6xx
→
Simulation mode active
601
S: POS. ZERO-RETURN
! # 601
0x53
UNCERTAIN
Sensor
conversion
not accurate
(measured
value from
sensor not
accurate)
Constant
Positive zero return
active
Cause:
Positive zero return is active.
!
Note!
This message has the highest display priority!
Remedy:
Switch off positive zero return.
Access:
BASIC FUNCTION
→
SYSTEM PARAMETER
→
CONFIGURATION
→
POS. ZERO RETURN (
→
OFF)
611
to
614
S: SIM. CURR. OUT. n
!: # 611 to 614
0x80
GOOD
O.K.
O.K.
Simulation IO
active
Cause:
Simulation current output is active.
Remedy:
Switch off simulation.
621
to
624
S: SIM. FREQ. OUT. n
!: # 621 to 624
0x80
GOOD
O.K.
O.K.
Simulation IO
active
Cause:
Simulation frequency output is active.
Remedy:
Switch off simulation.
631
to
634
S: SIM. PULSE n
!: # 631 to 634
0x80
GOOD
O.K.
O.K.
Simulation IO
active
Cause:
Simulation pulse output is active.
Remedy:
Switch off simulation.
641
to
644
S: SIM. STAT. OUT n
!: # 641 to 644
0x80
GOOD
O.K.
O.K.
Simulation IO
active
Cause:
Simulation status output is active.
Remedy:
Switch off simulation.
651
to
654
S: SIM. RELAY n
!: # 651 to 654
0x80
GOOD
O.K.
O.K.
Simulation IO
active
Cause:
Simulation relay output is active.
Remedy:
Switch off simulation.
671
to
674
S: SIM. STATUS IN n
!: # 671 to 674
0x80
GOOD
O.K.
O.K.
Simulation IO
active
Cause:
Simulation status output is active.
Remedy:
Switch off simulation.
691
S: SIM. FAILSAFE
!: # 691
0x48
0x49
0x4A
UNCERTAIN
Substitute set
(Substitute set
of failsafe
status)
O.K.
Low
High
Simulation failsafe
active
Cause:
Simulation of failsafe mode (outputs) is active.
Remedy:
Switch off simulation.
Access:
SUPERVISION
→
SYSTEM
→
OPERATION
→
SIM. FAILSAFE MODE (
→
OFF)
692
S: SIM. MEASURAND
!: # 692
0x60
0x61
0x62
UNCERTAIN
Simulated
Value
(manually
specified
value)
O.K.
Low
High
Simulation
measured value
active
Cause:
Simulation of the measured value is active.
Remedy:
Switch off simulation.
Access:
SUPERVISION
→
SYSTEM
→
OPERATION
→
SIM. MEASURAND (
→
OFF)
No.
Device status message
(local display)
PROFIBUS measured value status
Extended
diagnostic
message in the
PROFIBUS
master
Cause/remedy
Quality code (HEX)
Measured value status
Quality status
Quality substatus
Limits