Proline Promag 53 PROFIBUS DP/PA
Commissioning
Hauser
97
Recommended settings
Quick Setup “Batching”
HOME position
→
F
→
MEASURAND
→
O
→
QUICK SETUP
→
N
→
QUICK SETUP BATCHING (1005)
Function No.
Function name
Setting to be selected (
P
)
(to the next function with
F
)
1005
QUICK SETUP BATCHING/DOSING
YES
After
F
is pressed by way of confirmation, the
Quick Setup menu calls up all the subsequent
functions in succession.
▼
!
Note!
Some of the functions listed below (with a gray background) are configured automatically, i.e. by the measuring system.
6400
ASSIGN LOW FLOW CUTOFF
VOLUME FLOW
6402
ON-VALUE LOW FLOW CUTOFF
The recommended setting is contained on Page 94
in Function No. 6402.
6403
OFF-VALUE LOW FLOW CUTOFF
50%
6603
SYSTEM DAMPING
9
!
Note!
The parameter has to be optimized for highly
accurate and short filling processes: to do this, put
the setting to “0”.
6404
PRESSURE SHOCK SUPPRESSION
0 s
7200
BATCH SELECTOR
BATCH #1
7201
BATCH NAME
BATCH #1
7202
ASSIGN BATCH VARIABLE
VOLUME
7203
BATCH QUANTITY
0
7204
FIX COMPENSATION QUANTITY
0
7208
BATCH STAGES
1
7209
INPUT FORMAT
Value input
4700
ASSIGN RELAY
BATCHING VALVE 1
4780
TERMINAL NUMBER
Output (display only)
7220
OPEN VALVE 1
0% or 0 [unit]
7240
MAXIMUM BATCH TIME
0 s (= switched off)
7241
MINIMUM BATCH QUANTITY
0
7242
MAXIMUM BATCH QUANTITY
0
2200
ASSIGN (Main line)
BATCH NAME
2220
ASSIGN (Multiplex main line)
Off
2400
ASSIGN (Additional line)
BATCH DOWNWARDS
2420
ASSIGN (Multiplex additional line)
Off
2600
ASSIGN (Information line)
BATCHING KEYS
2620
ASSIGN (Multiplex information line)
Off
▼
Back to the HOME position:
→
Press and hold down the
X
key for longer than three seconds or
→
Repeatedly press and release the
X
key
→
Exit the function matrix step by step