Procedure
Set
mA Output Direction
as desired.
Option
Description
Normal (default) Appropriate when your application needs to distinguish between forward flow and
reverse flow.
Absolute Value
Appropriate when your application does not need to distinguish between forward flow
and reverse flow.
Important
mA Output Direction
interacts with
Lower Range Value
(LRV). The effect of
mA Output Direction
on the mA
Output varies, depending on whether LRV < 0 or LRV ≥ 0.
Related information
Configure Sensor Flow Direction Arrow
Effect of mA Output Direction on an mA Output
mA Output Direction
affects how the transmitter reports flow values via an mA Output. An mA Output is
affected by
mA Output Direction
only if
mA Output Source
is set to a flow variable.
The effect of
mA Output Direction
depends on the setting of
Lower Range Value
(LRV).
•
If
Lower Range Value
.
•
If
Lower Range Value
> 0, see
•
If
Lower Range Value
< 0, see
Configuration and Use Manual
Integrate the meter with the control system
MMI-20025166
March 2019
Configuration and Use Manual