Figure B-5: Connection over network
A. PC
B. Signal converter
C. 120-Ω, 1/2-watt resistors at both ends of the segment, if necessary
D. DCS or PLC
E. Transmitter, with wiring compartment and power supply compartment opened
Note
This figure shows a serial port connection. USB connections are also supported.
4. Start ProLink III.
5. Choose
Connect to Physical Device
.
6. Set parameters as shown here.
Parameter
Setting
PC Port
The number assigned to the COM port or USB port on your PC
Address
The HART address configured for this transmitter. The default is 0.
Parity
Odd
The transmitter automatically detects all other communications settings.
7. Set
Master
as appropriate.
Option
Description
Secondary Use this setting if a primary HART host such as a DCS is on the network.
Primary
Use this setting if no other primary host is on the network. The Field Communicator is a
secondary host.
8. Click
Connect
.
Using ProLink III with the transmitter
Configuration and Use Manual
March 2019
MMI-20025166
324
Micro Motion Model 5700 Transmitters with Configurable Outputs