Firmware V3.13
21.04.2021
430/466
•
•
9.7.4 Menu 3 Clock KR 160 E
CLOCK POS: XXXXX
1 Current Time
Move to menu 3-1
2 Defrost Timer
Move to menu 3-2
3 Toggle Setpoints
Move to menu 3-3
Menu 3-1 Current Time
CLOCK POS: XXXXX
Entry
Default
Date: XX dd.mm.yy
Display and entry of current weekday, date
dd.mm.yy
Time: hh.mm
Display and entry of current time
hh.mm
Daylight Saving X
Display and entry of automatic daylight saving
time change (Y/N)
↑, ↓, (Y/N)
Y
Menu 3-2 Defrost Timer
DEFR.TIMER POS: XXXXX
Entry
Default
Defrost Timer XXX
Defrost initiation via Input D11/12 (EXT) oder internal
(INT)
↑, ↓,
(EXT, INT)
EXT
Safe Defr Time XXX m
Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only); shown only when
paramter defrost timer = INT
0..120
60 min
Manual Defrost XXX
Status (ON/OFF) of auxiliary manual defrost *)
↑, ↓,
(ON/OFF)
OFF
Def.Tim.Z2 ®
Separate defrost timer for zone 2
Menu 3-2-a
Time is defined by time master (system centre / store computer / operator terminal) when CAN bus is
connected. Any entry made will then be overwritten by the defined value.
*) Parameter is
NOT
automatically set to ON at first start
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...