Firmware V3.13
21.04.2021
166/466
7.6 Terminal assignment of the 0..10 V analogue outputs
Only UA 410 E AC
Controller type
Terminal No.
Analogue output AO2
0..10 V
Analogue output AO1
0..10 V
All controllers
32
GND
–
31
or
–
30
–
GND
29
–
or
Function of the analogue outputs 0..10 V
.
DANGER
Warning about dangerous electrical voltage!
If mains power is connected to the analogue outputs,
this results in destruction of the controller!
ATTENTION
Malfunction due to interference:
All supply lines from and to the case controller must be shielded
(cable type: LiYCY)! If sensor cables are exclusively laid within the refrigerated case to be monitored
and sources of interference (e.g. parallel power lines) are not anticipated, then it is possible to
dispense with shielding. As a general rule, care should be taken to ensure that signal cables and
cables carrying mains voltage are routed in separate cable channels
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...