Firmware V3.13
21.04.2021
459/466
•
•
•
•
•
11.2 Individual allocation of priorities
It is possible in the case controller to allocate an individual priority for most alarms (parameter
Kühlstellenregler
prio
set to NO, menu 6-5). This makes it possible to address alarm destinations in a targeted way and to adjust
alarm signalling to individual requirements.
The priority on the controller side is used if the parameter
Kühlstellenregler prio
is set to
YES
(menu 6-5). It is
also always used for the alarm signalling in the event of failure of the control by the system centre / store
computer.
The values range of the priorities is extended to 0..99, so that now up to 100 alarm destinations can be
differentiated. This priority range is divided into 10 alarm groups (decades).
The 1 and 2 priorities (1, 11, ,21,...91 and 2, 12, 22,...92) are reserved for high priority alarms that affect the
alarm relays “PRIO1” and “PRIO2” as well as the LEDs “PRIO1” and “PRIO2” on the front of the store
computer.
The highest priority number in each group (9,19,29,...99) is reserved for low priority alarms that should only
generate local alarm signalling (e.g. open cold room door).
All other priority numbers are intended for low priority alarms.
The lowest priority number in each group (0,10,20,..90) is reserved for messages that are only recorded in
the message list.
If the priority is set to "–", no message is generated.
This division into alarm groups (decades) facilitates maintenance group oriented alarm management.
The alarm priorities --, 0..2 correspond to the remote alarm messaging concept of older store
computer versions with firmware versions <5.0. If priorities from 3..99 are configured in the controller,
the store computer must be updated to a firmware version of 5.0 or higher. Further information is
provided in the store computer operating manual.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...