Firmware V3.13
21.04.2021
368/466
•
Menu 3-3 Toggle Setpoints
TOGGLE POS: XXXXX
Entry
Default
Status XXX
Setpoint toggle for alternative set of setpoints
(setpoint set toggle)
Toggle Setp. XXX
Setpoint toggle via
- EXT digital input D21/22
- INT internal timer
- CAN CAN bus
- „--“ deactivated
Note: Care should be taken that the corresponding
digital input D21/D22 is set to SOLLW.UMSCH
(menu 6-2-4)
↑, ↓
(EXT, INT,
CAN, --)
EXT
Toggle interv. X m
The interval for the cyclical toggling between
standard and alternative setpoint data records; only
appears when the internal setpoint toggling is
activated (menu 3-3).
--, 10..60
-- min
Alt ON: xxxxx hh:mm
Start time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu
3-3)
↑, ↓
(Mo-Su) or numbers (hh:mm)
Mo-Su
21:00
AltOFF: xxxxx hh:mm
End time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu
3-3)
Mo-Su
05:00
Alt ON: xxxxx hh:mm
Start time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu
3-3)
↑, ↓
(Mo-Su) or numbers (hh:mm)
Su
05:00
AltOFF: xxxxx hh:mm
End time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu
3-3)
Su
21:00
...
A total of 7 different ON, OFF toggle times can be
entered. Toggle time will only be obeyed when a
matched pair
of ON and OFF time is set.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...