Firmware V3.13
21.04.2021
130/466
•
•
•
•
•
•
6.3.1 Status LEDs
Function
Colour
LED
Description
1
230 V AC
Digital
inputs
red
LED2
LED3
LED4
LED5
ON: Digital input 1 is activated (terminals D11/D12)
ON: Digital input 2 is activated (terminals D21/D22)
ON: Digital input 3 is activated (terminals D31/D32)
ON: Digital input 4 is activated (terminals D41/D42)
ATTENTION: External voltage can be present at these terminals!
2
230 V AC
Relay
outputs
green
LED6
LED7
LED8
LED9
LED10
LED11
LED12
ON: Relay 1 is switched (terminals 15/16/18) *
ON: Semi−conductor relay 2 (EEV1) is switched (terminals 23/24)
ON: Semi−conductor relay 3 (EEV2) is switched (terminals 33/34) *
ON: Relay 4 is switched (terminals 43/44)
ON: Relay 5 is switched (terminals 53/54)
ON: Relay 6 is switched (terminals 63/64)
ON: Relay 7 is switched (terminals 73/74)
ATTENTION: External voltage can be present at these terminals!
3
Transistor
outputs
green
LED13
LED14
ON: Transistor output 1 is switched (terminals 81..83)
ON: Transistor output 2 is switched (terminals 91..93)
4
LIFE
green
LED15
Controller with 8-pole DIP switch
FLASHING: Active lamp, controller is supplied with power, processor is running or controller
is in firmware update mode (all coding switches 1..8 of DIP S3 are ON), for details see
chapter
Update für Regler mit 8-poligem DIP-Schalter
OFF: Power supply interrupted or device defective
Controller with 9-pole DIP switch
FLASHING: Active lamp, controller is supplied with power, processor is running
OFF: Power supply interrupted or device defective or controller is in firmware update mode
(coding switch 9 of DIP S3 is ON), for details see chapter
Update für Regler mit 9-poligem
5
CAN bus
orange
LED1
FLASHING: LED always flashes when data are being exchanged via the CAN bus with the
system centre / store computer.
OFF: CAN bus connection interrupted or CAN bus defective
DANGER
Warning about dangerous electrical voltage! Danger of electric shock!
The device must never be
operated without its case. Before opening the case, the device must be disconnected from the power
supply.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...