Firmware V3.13
21.04.2021
69/466
•
•
•
•
Start of the defrosting
The defrosting can be initiated in 4 ways:
Using the internal clock
(except UK 100 E or KR 160 E)
Using an external week timer
via digital input D11/D12 (factory setting).
The defrost is activated via digital input 1(terminals D11/D12), its function can be configured using the
Inv.
D1
parameter in menu 6-2-4. The following cases are possible:
External defrost (master/slave mode not active):
The defrost signal for the external defrost must be present for as long as the maximum duration of the
defrost. The defrosting is also finished as soon as the external request is removed. A defrost termination
while the defrost signal is present is always possible via the evaporator sensors (if the defrost termination
temperature is exceeded).
External defrost in master/slave mode:
The defrost signal may only be present for a short time, as it only takes over the function here for starting
the defrost. The safe defrost time is realised using the internal
Sicherheitszeit
parameter. The external
signal must always be shorter than the internal safe defrost time.
Using a command via the CAN bus (manual or higher level control, e.g. Combi Gateway)
In all cases, it is checked whether the conditions for defrosting are met before defrosting is initiated. The
conditions are:
evaporator temperature < defrost termination temperature
In the case of defrost on demand: Defrost counter = 1
There is no
Sensor fault EEV1/2
or
emerg.cut-out SH Z1/2
alarm.
Using a command from the pack controller via the CAN bus
The defrost (hotgas defrost) is initiated without checking conditions.
A further defrost cannot be started until the safe defrost time (defrost parameters) has elapsed,
even if the defrost has already been terminated via the evaporator temperatures. If possible, the
defrost time should not be between 02:00 and 03:00 in order to avoid problems with missing or
doubled defrost during the changeover between summer and winter time.
Warning about dangerous electrical voltage!
Danger of electric shock! BEFORE
connecting and disconnecting, it must be checked that
no
voltage is present
at the 230 V AC digital inputs!
The controller and connected live parts are still energised!
The defrost is also prevented for the controller types UA 121 E, UA 131 E and UR 141 TE if the
following conditions are all met:
1.) A temperature alarm is pending and/or the alarm delay is set to 0 minutes.
2.) The evaporator temperature R1.1 and/or R1.3 is above the specified setpoint for the return air.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...