Firmware V3.13
21.04.2021
206/466
•
•
9.1.4 Menu 3 Clock UA 121 E
CLOCK POS: XXXXX
1 Current Time
Move to menu 3-1
2 Defrost Timer
Move to menu 3-2
3 Toggle Setpoints
Move to menu 3-3
Menu 3-1 Current Time
CLOCK POS: XXXXX
Entry
Default
Date: XX dd.mm.yy
Display and entry of current weekday, date
dd.mm.yy
Time: hh.mm
Display and entry of current time
hh.mm
Daylight Saving X
Display and entry of automatic daylight saving
time change
(Y/N)
↑, ↓, (N/Y)
Y
Menu 3-2 Defrost Timer
DEFR.TIMER POS: XXXXX
Entry
Default
Defrost Timer XXX
Defrost initiation via Input D11/12 (EXT) or
internal (INT)
↑, ↓, (EXT, INT)
INT
Safe Defr Time XXX m
Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX
Status (ON/OFF) of auxiliary manual defrost *)
↑, ↓, (ON/OFF)
OFF
Def.Tim.Z2 →
Separate defrost timer for zone 2
Menu 3-2-a
Defr. 1 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter
defrost timer
= INT
↑, ↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
01:00
Defr. 2 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter
defrost timer
= INT
↑, ↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
07:00
Defr. 3 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter
defrost timer
= INT
↑, ↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
13:00
Defr. 4 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter
defrost timer
= INT
↑, ↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
19:30
...
Defr. 14 xxxxx hh:mm
Time is defined by time master (system centre / store computer / operator terminal) when CAN bus is
connected. Any entry made will then be overwritten by the defined value.
*) Parameter is automatically set to ON at first start for the duration of the safe defrost time.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...