Firmware V3.13
21.04.2021
367/466
•
Menu 3-2-a Def.Tim.Z2
DEFR.TIMER POS: XXXXX
Entry
Default
Defrost Timer XXX
Setting for how temperature zone 2 should
defrost:
- MitZ1 Together with zone 1
- INT Internally
- EXT Externally – the defrost of both
temperature
zones is started simultaneously via the external
signal
↑, ↓
(ViaZ1(ViaZ1,EXT,
INT)
ViatZ1
Safe Defr Time XXX m
Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120
60 min
Manual Defrost XXX
Status (ON/OFF) of auxiliary manual defrost *)
↑, ↓
(ON/OFF)
OFF
Defr. 1 xxxxx hh:mm
Defrost start time for internal defrost; weekday,
time of day; shown only when paramter
defrost
timer
= INT
↑, ↓
(Mo-Su) or numbers (hh:mm)
Mo-Su
01:00
...
Defr. 14 xxxxx hh:mm