6.6 Firmware update
The case controller is supplied with the current firmware, ready for operation. Future software versions can be
loaded into the case controller as required by means of a firmware update, and thus updated.
ATTENTION
Damage to equipment and goods!
Before the firmware update the affected component, i.e.
equipment must be brought into a safe state as the deactivation of the controller during the firmware
update can have undesired effects on the component, i.e. equipment.
Danger data loss!
The loading of software via firmware update must not be interrupted. The power
cable and USB A-B cable must not be disconnected during the firmware update. It must be ensured
that power is supplied throughout the entire procedure. An interruption of the firmware update can
result in an inoperative controller. In some cases a change of firmware version can lead to the loss of
all the setpoints in the case controller. As a precaution, the settings should be backed up by saving
them to the LDSWin PC software, prior to the update. After the firmware update the backup settings
can be reloaded into the case controller from LDSWin.
A software update is only to be carried out by trained staff or factory-side by the manufacturer. For
further details about the current firmware see the
.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...