Firmware V3.13
21.04.2021
286/466
•
•
Menu 2-6-1 Pane Mode
Selection is made according to entry. Checkmark shows current setting.
PANE HTR POS: XXXXX
Entry
Default
Fixed run time √
√
Enthalpy-ctrl rtm
Menu 2-6-2 Pane Setpoints
SETPOINTS POS: XXXXX
Entry
Default
Mod: xxxxxxxxxxxx
Displays set frame mode (Menu 2-5-1)
fixed run time
Pane On Time XX m
Pane heater on time. When making entry, make
sure that the corresponding digital input D31/D32
is set to PANE SWITCH (Menu 6-2-4)
0..120
60 min
Run Time XXX %
Fixed on time, shown only when mode set to Fixed
OT (Menu 2-5-1)
--, 0..100
0 %
emerg.run time XXX %
On time in loss of huimidity or room air
temperature (via CAN bus); shown only when
mode set to Enthalpy Control (Menu 2-5-1)
--, 0..100
0 %
enthalp. offs. XXX %
Offset for on time when enthalpy control is
activated (via CAN bus); shown only when mode
set to Enthalpy Control (Menu 2-5-1)
-50..50
0 %
Invert Output xxx
Inversion of the function of the frame heater output
(terminals 91/92)
↑,↓,
(ON/OFF)
ON
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...