Firmware V3.13
21.04.2021
163/466
Mode of operation „positive”
means that operation of the relay is not inverted:
The relay is energized when the controller activates the function output (e.g. cooling = ON). (This
means that the contact of a normally open relay is closed.)
The relay is not energized when the controller deactivates the function output (e.g. cooling = OFF).
(This means that the contact of a normally open relay is open.)
Mode of operation „inverted”
means that operation of the relay is inverted:
The relay is not energized when the controller activates the function output (e.g. alarm = ON). (This
means that the contact of a normally open relay is open.)
The relay is energized when the controller deactivates the function output (e.g. alarm = OFF). (This
means that the contact of a normally open relay is closed.)
** The function for the frame heater / pane heater can be configured via the parameter „Invert
Output“ (menü 2-5-2 / menu 2-6-2).
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...