Firmware V3.13
21.04.2021
317/466
•
•
•
Menu 2-1-2 Zone 2
COOLING 2POS: XXXXX
Entry
Default
Setpoint R4.2 XXX °C
Room air temperature setpoint
--, -10..30
5 °C
Hystersis R4.2 X K
Room air temperature hysteresis setpoint; shown only
when on-off control is set (Menu 2-1-2)
1..8
2 K
Superheat XXX K
Superheat setpoint Zone 2
0..20
6 K
Min. SH XX K
Minimum superheat setpoint, below which cooling relay
switches off in Zone 2. I-sum (not I-part) is set to zero
when the
Reset I-Sum
parameter is set to ON.
0..10
2 K
Two pos.ctrl XXX
Switch between on-off control (ON) and continuous
control (OFF)
↑, ↓,
(ON/OFF)
OFF
MOP-point XXX °C
Starting setpoint for MOP mode
--, -50..50
– °C
Cool. on AOUT XXX%
Kühlung eingeschaltet: fester Wert 0..10 V für
Analogausgang AO2; nur sichtbar, wenn von DIP-
Schalter S3 der Kodierschalter 6 auf ON steht, siehe
Kapitel
Funktionsweise der Analogausgänge 0..10 V.
0..100
80 %
Cool. off AOUT XXX%
Kühlung ausgeschaltet: fester Wert 0..10 V für
Analogausgang AO2; nur sichtbar, wenn von DIP-
Schalter S3 der Kodierschalter 6 auf ON steht, siehe
Kapitel
Funktionsweise der Analogausgänge 0..10 V.
0..100
50 %
Menu 2-1-3 Zone 1T Toggle
COOLING 1APOS: XXXXX
Entry
Default
Setpoint R4.1 XXX °C
Room air temperature setpoint
--, -10..30
3 °C
Hystersis R4.1 X K
Room air temperature hysteresis setpoint; shown
only when on-off control is set (Menu 2-1-1)
1..8
1 K
Ht. Cir. Setp.
Heating circuit control setpoint; shown only when
single-zone operation is set (Menu 6-1)
--, -10..30
3 °C
Ht. Cir. Hyst.
Heating circuit control hysteresis setpoint; shown
only when single-zone operation is set (Menu 6-1)
1..8
1 K
Menu 2-1-4 Zone 2T Toggle
COOLING 2APOS: XXXXX
Entry
Default
Setpoint R4.2 XXX °C
Room air temperature setpoint
--, -10..30
3 °C
Hystersis R4.2 X K
Room air temperature hysteresis setpoint; shown
only when on-off control is set (Menu 2-1-2)
1..8
1 K
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...