Firmware V3.13
21.04.2021
28/466
•
•
•
•
Two-zone operation
- only UA 400 E CC / UA 410 E AC
two temperature zones
2 pilot cases
In two-zone operation, the temperature and superheat are controlled
separately
for each refrigerated case. In
addition to the conventional end of defrosting, there is the possibility of returning the two refrigerated cases to
the cooling operation together after a defrost. The master/slave mode in two-zone operation must be activated
for this; see
. Only one evaporator sensor per evaporator is intended.
One-room.air-sensor operation
- Controller type UR 141 NE, UR 141 TE - only UA 400 E CC / UA 410 E AC
In two-zone operation, the room controllers can control both zones via
one
common room air sensor. In this
operating mode, the room air sensor for the first zone (R4.1) is used for the room temperature control of both
zones. The superheat control of both zones continues to be performed independently. This operating mode is
suitable e.g. for the use of two independently controlled evaporators within one room.
In order to activate operation the following
must
apply
two-zone operation is set (menu 6-1) and
- the cold room temperature setpoint of the second zone (menu 2-1-2) is set to “--“.
The alternative cold room temperature setpoint of the second zone (e.g. night-time value) has
no
function in this operating mode.
If the transition to cooling should take place simultaneously for both zones after a defrost, the
master/slave mode must be activated for this case controller.
The room air sensor of the second zone (R4.2) is
not
used for regulation in this operating mode;
nevertheless, if it is plugged in, temperature monitoring takes place for this sensor.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...