Firmware V3.13
21.04.2021
298/466
•
Menu 6-2-7 EEV Controller Zone 1
EEV ZONE 1 POS: XXXXX
Entry
Default
Pc Z 1: XX.XX
Temperature control Zone 1, P-part
0..99.99
7.00
Ic Z 1: XX.XX
Temperature control Zone 1, I-part
If parameter I
c
is reduced, internal learned value
(sum
of I-part) is deleted and re-learned in due course.
0..99.99
0.30
Dc Z 1: XX.XX
Temperature control Zone 1, D-part
0..99.99
5.00
offs OD cab. XX %
Percentage valve opening degree offset for
temperature control
If offset is changed, internal learned value (sum of I-
part) is deleted and re-learned in due course.
0..100
30 %
Psh Z 1: XX.XX
Superheat control Zone 1, P-part
0..99.99
5.00
Ish Z 1: XX.XX
Superheat control Zone 1, I-part
If parameter I
sh
is reduced, internal learned value
(sum
of I-part) is deleted and re-learned in due course.
0..99.99
0.10
Dsh Z 1: XX.XX
Superheat control Zone 1, D-part
0..99.99
5.00
offs OD SH XX %
Percentage valve opening degree offset for
superheat control
If offset is changed, internal learned value (sum of I-
part) is deleted and re-learned in due course.
0..100
10 %
emerg.c-o OD XX %
Maximum valve opening degree
0..50
20 %
delay min SH XX s
Delay on drop of superheat below set minimum
9..600
9 sec
setuptime XX.X m
Setup time following the switching on of the
controller or following a defrost or in the event of a
blockade of the regulation.
The value entered must not be less than the current
”inject.time”
parameter, otherwise the smallest valid
value will be used.
Further details about “Fixed valve opening degree in
pumpdown/feed-in phase” see chapter
opening degree in pumpdown/feed-in phase
0..100.0
6.0 min
inject.time XX.X m
Injection time following the switching on of the
controller or following a defrost or in the event of a
blockade of the regulation.
The value entered must not be greater than the
current
”setuptime”
parameter, otherwise the largest
valid value will be used.
Further details about “Fixed valve opening degree in
pumpdown/feed-in phase” see chapter
opening degree in pumpdown/feed-in phase
0..100.0
5.0 min
•
•
This menu is only visible if
the “Master” mode is activated in the system centre, i.e.
the “Superuser mode” is activated in the store computer
.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...