Firmware V3.13
21.04.2021
85/466
1.
2.
a.
a.
b.
c.
3.
a.
i.
ii.
iii.
4.
5.
•
•
•
Example configuration:
Specify the sequence in which the controllers should defrost (e.g. first the controllers with the addresses 11
and 12, then 22, 25 and 27, then 5 and 28).
The controllers that should defrost first belong to group 1,
1. for one of these controllers (e.g. address 11), under 2 Setpoints - 2 Defrost - 1 Zone 1:
set
FA-Funktion
as "Master"
2. for all other controllers in group 1 (e.g. UA with address 12), under 2 Setpoints - 2 Defrost - 1 Zone 1:
set
FA-Funktion Slave
and
FA-Gruppe
1 and
FA-Master
(CAN bus address of the master controller; "11" in this example).
The controllers that should defrost next receive the group number 2,
for all these controllers (controllers 22, 25 and 27 in this example):
set
FA-Funktion Slave
and
FA-Gruppe
2 and
FA-Master
(CAN bus address of the master controller; "11" in this example).
Proceed in the same way for other groups (controllers 5 and 28 in this example) and enter the respective
group number (here group number 3 and following).
If required, a wait time can be set on the master controller (11 in the example) for the period between group
defrosts under 2 Setpoints – 2 Defrost – 1 Zone 1 -
FA-Warte
z.
Further actions for the parametrisation of the consecutive defrost
The initiation of an additional, separate defrost (manual, external, internal, CAN) on a consecutive defrost
slave should be avoided (defrost times set to “—“), however, it can nevertheless be performed if needed.
Safe defrost times, drip and wait times and defrost on demand can be assigned individually for every
controller of the consecutive chain.
The parameter “
FA-Master
” must not be set to CAN bus addresses that do not exist. If the controller does
not exist or is unable to execute a defrost, the alarm “
No Defrost
” is generated.
Group numbers
The consecutive defrost master is automatically in group 1 as it starts the defrost, and if the conditions are met,
will also defrost itself directly in the process.
The number of the group specifies the order of the defrosting. Numbers can also be skipped. If one group has
finished defrosting, the group with the next highest number will be automatically defrosted following the elapse
of the wait time set on the master. By remaining in regular contact with the other controllers on the CAN bus,
the CD master has an overview of all available CD slaves and the corresponding group numbers. The
controllers must be configured so that the consecutive defrost can be carried out in the desired sequence.
Actual values
Menu 1-3 contains the following actual values for the consecutive defrost
The parameter "
FA Anz. Sl.
" on the consecutive defrost master shows the number of slaves known to the
master. The parameter "
FA verl Sl."
shows "
lost
" consecutive defrost slaves on the consecutive defrost master:
If a previously available consecutive defrost slave can no longer be contacted, the CAN bus address of the
consecutive defrost slave which the master first lost contact with during the last defrost is shown here.
Otherwise (normal case), ”--“ is displayed.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...