Firmware V3.13
21.04.2021
43/466
5.7.3 Continuous temperature control by supply and return air temperature
Controller types UA 121 E, UA 131 E, UA 141 E
Control is made by two temperature sensors (supply air or return air sensor of pilot case). Cooling can take
place in single-zone or two-zone mode. In single-zone mode, sensors Ry.1 act on both relays 1 and 2 of the
expansion valves. The two relays are actuated at separate times (see Section
R2.1: Supply air sensor (Terminal Z11/12)
R4.1: Return air sensor (Terminal Z21/22)
R5.1: Evaporator inlet sensor (Terminal Z41/42)
R6.1: Evaporator outlet sensor (Terminal Z51/52)
Expansion valve 1: Relay for expansion valve 1 (Terminal 23/24)
Expansion valve 2: Relay for expansion valve 2 (Terminal 33/34)