Supply air/return air mode
The supply air setpoint is toggled as a function of return air temperature as follows:
Example 1:
Return air
Actual
< Return air
Setpoint
- 2K:
Supply air temperature is controlled to return air setpoint.
Example 2:
Return air
Setpoint
- 2K < Return air
Actual
< Return air
Setpoint
Setpoint is toggled between supply air and return air setpoint in linear steps (see diagram below).
Example 3:
Return air
Actual
> Return air
Setpoint
:
Supply air is controlled to supply air setpoint.
When supply air temperature equals the current setpoint, opening duration of the expansion valves is reduced
to the time required to maintain the current state. If only one of the two sensors is fitted (supply air or return
air), control is made exclusively by that sensor.