Firmware V3.13
21.04.2021
313/466
•
•
Menü 1-5 Alarm
ALARM XXXXX
Alarm Relay XXX
Displays current OFF/ON status of alarm output Terminal 15/16/18
Hi Temp Setp.1 XX °C
Displays high temperature setpoint Zone 1
Lo Temp Setp.1 XX K
Displays low temperature setpoint Zone 1
Hi Temp Setp.2 XX °C
Displays high temperature setpoint Zone 2; shown only when two-zone operation
is set (Menu 6-1)
Lo Temp Setp.2 XX K
Displays low temperature setpoint Zone 2; shown only when two-zone operation is
set (Menu 6-1)
Coldroom Door 1 XXX
Displays current OFF/ON status of coldroom door input Terminal D31/D32
Coldroom Door 2 XXX
Displays current OFF/ON status of coldroom door input Terminal D21/D22
Menu 1-6 Frame Heater
MODE XXXXX
Frame Heater XXX
Displays current OFF/ON status of frame heater output Terminal 91/92/93
Run Time XXX %
Displays current frame heater on time
Humidity XXX %
Displays current room air humidity (transmitted via CAN bus from VS pack controller
with fitted humidity sensor)
Room temp. XX °C
Displays current room air temperature (tranmitted via CAN bus from VS pack controller
with fitted room air temperature sensor)
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...