4
. Exit from the menu
1 Refrigeration point
by tapping the
ESC
button once and select menu
6 Configuration
- 2 Controller
.
6 Configuration - 2 Controller
REGLER POS: XXX
1 Type and version
Type, serial number and Master / Slave (ON/OFF)
2 Temperature display
Adjustment of the displayed temperature value
3 Alarm delay
Input of an alarm delay time
4 230 V inputs
230 V inputs
5 Sensor type
Selection of the temperature sensor of the type L243, K277 or 5K3A1
5.
Select menu
6 Configuration - 2 Controller
-
3 Alarm delay
.
6 Configuration – 2 Controller – 3 Alarm delay.
ALARMVERZ. POS: XXX
Fühlerbruch XXm
Alarm delay for sensor fault
Über/Unter Tmp XXXm
Alarm delay for high temperature or low temperature
keine Abtauung XXXh
Alarm is tripped if no defrost is performed within this configurable time.
Selbsthaltung N
NO: Automatic reset of non-transient alarms
YES: Alarms must be reset manually
Exit the menu by tapping the
ESC
button once.
6.
Select menu
6 Configuration – 2 Controller – 6 Analogue Inputs
.
6 Configuration - 2 Controller - 6 Analogue Inputs
Ain1 aktiv x
Use analogue input Z1 (=Y), do not use (=N)
Kältem.Z 1 xxxx
Selection of refrigerant zone 1
ND Z1 Min xxx bar
Smallest pressure value for pressure monitoring at 4 mA
ND Z1 Max xxx bar
Largest pressure value for pressure monitoring at 20 mA
...
...
AIN2 aktiv x
Use analogue input Z2 (=Y), do not use (=N)
Kältem.Z 2 xxxx
Selection of refrigerant zone 2
Fkt. AIN2 xxxxx
Function of the analogue input Z2:t0Z2 Only for recording t0Z2Reg For
regulation
HD Z2 Min xxx bar
Smallest pressure value for pressure monitoring at 4 mA
HD Z2 Max xxx bar
Largest pressure value for pressure monitoring at 20 mA
...
...
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...