Firmware V3.13
21.04.2021
463/466
•
•
•
•
UA 400 E CC / UA 401 E CC / UA 410 E AC
Real-time clock
Only UA 410 E AC:
With power reserve and lithium cell (for details, see ""Transport and storage")
Accuracy: typical 12 minutes per year at 25 °C
Field bus interface
CAN bus, floating output
Data ports
DISPLAY: BT 300 x operator interface and up to four BT 30 temperature displays
USB port
1. for the direct parametrisation of the case controller via LDSWin or 2. for
performing a firmware update of the case controller or 3. for the parametrisation of
system components via CAN bus using LDSWin.
Monitoring function
Watchdog
Environmental conditions
Transport and storage
Only UA 410 E: The controller contains a 3 V lithium cell (design type CRC 2450
N, shelf life 10 years) with capacity of 540 mAh and lithium content of 0.16 g.
The battery complies with the UN3090 requirements for lithium metal cells. No
special markings or measures for transport and storage are required up to a
lithium amount of 2.5 kg per package (total amount for pallets or containers).
Temperature range
Transport: -20 °C ... +80 °C
Operation: 0 °C ... +50 °C
Temperature change
Transport: max. 20 K/h
Operation: max. 10 K/h
Relative humidity (non-condensing)
Transport: 5% ... 85%
Operation: 5% ... 85%
Shock according to DIN EN 60068-2-27
Transport and operation: 30 g
Vibration 10 Hz ... 150 Hz according to DIN EN
60068-2-6
Transport and operation: 2 g
Atmospheric pressure
Transport: 660 hPa ... 1060 hPa
Operation: 860 hPa ... 1060 hPa
Weight
approx. 680 g
Standards and Directives
Protection rating
IP20 (EN 60529)
Automatic operating mode
Mode of operation type 1.K
Software class A
EN 60730-1 Appendix A
CE conformity according to
Low Voltage Directive 2014/35/EU;
Official Journal of the EU L96, 29/03/2014, pages 357-374
EMC Directive 2014/30/EU;
Official Journal of the EU L96, 29/03/2014, pages 79-106
RoHS Directive 2011/65/EU;
Official Journal of the EU L174, 01/07/2011, pages 88-110
1)
Supply cables to analogue inputs / outputs must be shielded.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...