Firmware V3.13
21.04.2021
80/466
•
•
5.8.5.3 Necessary settings for the master / slave mode
Controller - Hardware
In order to activate the master/slave mode, the coding switch 4 on the DIP switch 3 on the case controller
must
be set to
ON
.
The change is only adopted when the controller is restarted (switched off and back on again).
Controller - Software
The activation of the Master / Slave mode can be checked in the menu 6-2-1.
5.8.5.4 Special features and constraints
All defrost relays are energized simultaneously at the commencement of defrosting. As defrosting proceeds,
the evaporator defrost relays are de-energized separately and exclusively as a function of defrost termination
temperature.
All the characteristics of the defrost function such as defrost on demand, defrost via CAN bus and manual
defrost are preserved by the master case controller and also need to be parameterised here (on the master).
The master / slave wiring is described in the chapter
Wiring of the master-slave function for defrost
Return to cooling mode is not however made until defrosting is completed on all synchronized cases.
Defrosting can be carried out on the master by inputting a signal to the defrost input.
Содержание Case Controller UA 4 E Series
Страница 23: ...Firmware V3 13 21 04 2021 23 466 For more details see chapter Operation UA 4xx E ...
Страница 135: ...Firmware V3 13 21 04 2021 135 466 Exit the menu by tapping the ESC button twice ...
Страница 157: ...Firmware V3 13 21 04 2021 157 466 Connection diagram UA 400 E CC One zode controller and two zone controller ...
Страница 158: ...Firmware V3 13 21 04 2021 158 466 Anschlussbild UA 401 E CC One zode controller ...
Страница 207: ...Firmware V3 13 21 04 2021 207 466 ...
Страница 216: ...Firmware V3 13 21 04 2021 216 466 SENSORS POS XXXXX Entry Default 5K3A1 Temperature range 0 100 C ...
Страница 277: ...Firmware V3 13 21 04 2021 277 466 ...
Страница 364: ...Firmware V3 13 21 04 2021 364 466 MODE POS XXXXX Entry Default Fixed run time Enthalpy ctrl rtm ...