Dresser Model 10C25 Series K Installation, Operation, and Maintenance Manual
© 2018 Natural Gas Solutions North America, LLC
Page 59 of 74
Periodic Check Tests
14.2
Pressure Differential Test Procedure
14.2.1
Pressure Differential Test Equipment
Perform differential testing by using the following test equipment specifications:
•
Use differential pressure test equipment with an indicating scale range of at least 20 inches of w.c.
•
Use a testing device with bypass valving that is pressure rated for the maximum metering line
pressure for the test.
•
Connect pressure lines to the 1/4 inch meter inlet and outlet pressure taps located on the meter
body, as shown in Figure 75.
•
(Optional) Permanently install differential test plugs in the pressure taps to facilitate testing.
•
(Recommended) Use a pressure gauge to verify pressure readings.
14.2.2
Differential Test Process
The meter is able to display the flow rate when it is operating at a fairly steady rate of flow (refer to
Section 11.4.)
WARNING
When the meter is pressurized, follow applicable safety rules and use appropriate personal protective
equipment.
1.
Install the pressure differential test equipment into the meter inlet and outlet differential taps (refer
to Figure 75)
. Follow the manufacturer’s instructions for proper installation and operating procedures.
On the upstream side of the meter, install a pressure gauge or other pressure standard if it is not
already a part of the test equipment.
2.
If possible, use the meter set valve(s) to adjust the flow rate in the lower capacity range or no less
than 25%
of the meter’s rated capacity. Let the flow rate stabilize.