3 - 2 5
3
Operation Modes
3.3 Hot Standby Redundancy
(Only for Dual Input & at Least Two UPSs)
7RSURYLGHFXVWRPHUVZLWKPRUHDSSOLFDWLRQFKRLFHVWKH836ZLWKGXDOLQSXWFRQ¿JXUDWLRQV
can have a hot standby redundancy function. If you use two UPSs and wish them to work
in hot standby redundancy mode, please connect the output of UPS1 to the bypass input of
UPS 2. Please see
Figure 3-23
.
For more information about the hot standby redundancy application, please contact service
personnel.
In normal condition, it is the UPS 2 inverter that supplies power to the critical loads. Both
UPS 1 & UPS 2 tri-color LEDs illuminate green.
When the UPS 2 inverter becomes abnormal, the UPS 2 will automatically transfer to
bypass mode and the UPS 1 inverter will supply power to the critical loads. Under such
circumstances, the UPS 1 tri-color LED illuminates green and the UPS 2 tri-color LED
illuminates yellow.
BYPA.
MAIN
Power Module 1
Power Module 2
Power Module...
UPS 1
MAIN
Power Module 1
Power Module 2
Power Module...
UPS 2
Q1
Inverter
Rectifier
Static Switch
Static Switch
Q5
Q2
(OFF)
(ON)
Q3
Q4
Q1
Inverter
Converter
Converter
Rectifier
Static Switch
Static Switch
Q5
Q2
(OFF)
(ON)
Q3
Q4
LOAD
(Figure 3-23: Hot Standby Redundancy Diagram (only for Dual Input & at Least Two UPSs))
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......