6 - 1 7
6
UPS Operation
(b) Dual Input:
$IWHUWKHVWHSVPHQWLRQHGDERYHLV¿QLVKHGLWZLOOEHWKHE\SDVVVRXUFHWRVXSSO\
power to the connected loads. Once the bypass start-up procedures are completed,
the following screen appears and the tri-color LED indicator remains yellow.
UPS-1.1
Bypass
2019-Mar-01
09:30
EVENT LOG
10 mins
Bypass
Load
0 %
Mains
6.2.4 Manual Bypass Mode Start-up Procedures
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
)RUSDUDOOHODSSOLFDWLRQLI\RXMXVWZDQWWRRSHUDWHDVSHFL¿F836EXWQRWDOO
parallel ones, please contact service personnel.
3. Please note that you can turn on the external maintenance bypass cabinet’s
manual bypass breaker (Q3) only when the UPS needs maintenance. In
manual bypass mode, power supply of the connected critical loads comes from
the manual bypass and the output is not protected. Please ensure that the
bypass AC source is normal.
4. In Manual Bypass mode, power supply of the critical loads comes from the
manual bypass; thus, maintenance personnel can perform maintenance without
interrupting the power supplying to the critical loads.
5. In manual bypass mode, ensure that all of the breakers and switches (except
the external maintenance bypass cabinet’s manual bypass breaker (Q3)) are
in the
OFF
position, and use a voltmeter to check if there is any high voltage
LQVLGHWKH8362QO\DIWHU\RXKDYHFRQ¿UPHGWKDWWKHUHLVQRKLJKYROWDJHLQ
the UPS can service personnel perform UPS maintenance.
6. During UPS maintenance process, to avoid electric shock, do not touch the
following parts:
(a) The external maintenance bypass cabinet’s AC Input terminal block, Bypass
Input terminal block, UPS Output terminal block, Battery Input terminal
block, grounding terminals and any copper bars connected to the external
maintenance bypass cabinet’s Manual Bypass Breaker (Q3).
(b) Every external battery cabinet’s battery input terminal block.
These parts mentioned above may carry high voltage
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......