Communication Interfaces
4.1.3 Parallel Ports
1. The parallel ports (see
Figure 4-9
) are used to connect parallel UPSs to increase the
system capacity and redundancy.
2. You can parallel at maximum eight UPS units.
For 1000kW UPS, you can parallel at maximum 8 UPS system cabinets, and each UPS
system cabinet can connect to up to 5 power modules.
For 1250kW UPS, you can parallel at maximum 8 UPS system cabinets, and each UPS
system cabinet can connect to up to 6 power modules.
3. With the provided parallel cable, UPSs with the same capacity, voltage, frequency
and version can be paralleled. For version information, please refer to
7.10.8 Version
.
Please only use the provided parallel cable to parallel the UPS units; otherwise, parallel
functions will fail.
WARNING:
The provided parallel cable is placed in the accessory package. Using other
types of cables to connect the parallel UPSs may cause parallel failure,
malfunctions and accidents.
PARALLEL
(Figure 4-9: Parallel Ports)
4.1.4 Parallel Switch
PARALLEL
SWITCH
ON
OFF
(Figure 4-10: Parallel Switch)
When paralleling UPSs, you should set up the parallel switch shown in
Figure 4-10
to
activate parallel function. The parallel switch includes two DIP switches. To turn on a DIP
VZLWFKVHWWKH',3VZLWFKWRWKHGRZQSRVLWLRQ7RWXUQRႇD',3VZLWFKVHWWKH',3VZLWFK
to the up position.
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......