4 - 1 6
Ultron DPM series
OD1
OD1
OD3
OD3
OD5
OD5
OD2
OD2
ODn
ODn
OD4
OD4
OD6
OD6
n
= 1, 2, ...6
Relay
(Figure 4-25: Output Dry Contacts_ Pins
’
Location and Wiring Diagram)
No.
Event
Description
1
Load on inverter
The UPS works in normal mode.
2
Load on bypass
The UPS works in bypass mode.
3
Battery discharge/ Main
input NOK
When the main AC source fails, the batteries
supply power to the critical loads.
4
Low battery
When the UPS runs in battery mode, battery
voltage is lower than the setup limit 440Vdc.
5
Bypass input NOK
The bypass voltage, frequency or phase
sequence is abnormal.
6
Battery test fail or battery
missing
During the battery test, the battery voltage is out
of the setup limit.
7
Internal communication
failure
The #n power module’s internal communication is
abnormal.
8
External parallel
communication loss
In parallel mode, parallel communication is
abnormal.
9
Output overload warning/
shutdown
The UPS is overloaded or the UPS shuts down to
let the bypass supply power to the critical loads.
10
Power module fault
shutdown
The #n power module has abnormalities and it
shuts down the UPS to let the bypass supply
power to the critical loads.
11
Power module warning
The #n power module has abnormalities but the
UPS still runs in normal mode.
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......