5 - 5 1
5
Installation and Wiring
y
The external battery cabinet’s protective device installation methods are as follows.
Option 1: Installation of a 2-pole DC circuit breaker or DC isolated switch (voltage per
SROH9GFFRQQHFWHGLQVHULHVZLWKD'&IXVHYROWDJH9GF
-
+
UPS
-
+
External
Battery
Cabinet
DC Fuse
2-Pole DC Circuit Breaker
or DC Isolated Switch
(Figure 5-43: Installation of a 2-Pole DC Circuit Breaker or
DC Isolated Switch Connected in Series with a DC Fuse)
2SWLRQ,QVWDOODWLRQRIDSROH'&FLUFXLWEUHDNHUYROWDJHSHUSROH9GF
-
+
UPS
-
+
External
Battery
Cabinet
2-Pole DC Circuit Breaker
(Figure 5-44: Installation of a 2-Pole DC Circuit Breaker)
y
To save on your costs and installation space, the parallel UPSs can share their con-
nected external battery cabinet(s). For relevant information, please refer to
3.4 Com-
mon Battery (Only for Parallel UPSs Connected to the Same External Battery
Cabinet(s))
and
5.4.5 Parallel Units Wiring
.