3 - 2 1
3
Operation Modes
3.2.8 Bypass Mode_ Dual Input_ Parallel Units
In Bypass mode (parallel), when all inverters encounter abnormal situations such as
overload, short circuit, abnormal output voltage or low battery, they will automatically shut
themselves down. Meanwhile, if all parallel UPSs detect the bypass AC source is normal,
they will automatically switch to Bypass mode to protect the connected critical loads from
power interruption. The critical loads will be equally shared by all parallel units. After the
abnormalities mentioned above are eliminated, the parallel UPSs will switch back to On-
Line mode from Bypass mode. During Bypass mode (parallel), each UPS’s tri-color LED
illuminates yellow and each UPS’s LCD shows the text '
Bypass
' in the lower right corner.
Please refer to
Figure 3-20
for the path of electrical power through the parallel UPSs in
Bypass mode.
MAIN
Power Module 1
Power Module 2
Power Module...
Q1
Inverter
Converter
Rectifier
Static Switch
Q5
(OFF)
Q4
MAIN
Power Module 1
Power Module 2
Power Module...
Q1
Q2
Q2
Inverter
Converter
Rectifier
Static Switch
Q5
(OFF)
Q4
UPS 1
UPS 2
LOAD
BYPA.
Q3
Static Switch
(ON)
Q3
Static Switch
(ON)
BYPA.
(Figure 3-20: Bypass Mode Diagram_ Dual Input Parallel Units)
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......