10
Troubleshooting
1 0 - 1 3
No.
Alarm
Message
Possible Cause
Solution
93
PWR MODULE
#n AMBIENT
THERMAL
SENEOR NOT
INSTALLED
1. The sensor cable of the
power module #n is loose.
2. The circuit board of the
power module #n is
abnormal.
Please contact service personnel for
assistance.
94
PWR MODULE #n
DC CAP THERMAL
SENEOR NOT
INSTALLED
1. The sensor cable of the
power module #n is loose.
2. The circuit board of the
power module #n is
abnormal.
Please contact service personnel for
assistance.
95
PWR MODULE
#n PFC IGBT
THERMAL
SENEOR NOT
INSTALLED
1. The sensor cable of the
power module #n is loose.
2. The circuit board of the
power module #n is
abnormal.
Please contact service personnel for
assistance.
96
PWR MODULE
#n INV IGBT
THERMAL
SENEOR NOT
INSTALLED
1. The sensor cable of the
power module #n is loose.
2. The circuit board of the
power module #n is
abnormal.
Please contact service personnel for
assistance.
97
PWR MODULE
#n PFC DC/
DC THERMAL
SENEOR NOT
INSTALLED
1. The sensor cable of the
power module #n is loose.
2. The circuit board of the
power module #n is
abnormal.
Please contact service personnel for
assistance.
NOTE:
If the alarm still exists after the above possible causes are eliminated, please contact your
dealer or customer service.
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......