7 - 3 5
7
LCD Display & Settings
Standby
UPS-1.1
2019-Mar-01
09:30
UPS Setup
Test
EVENT LOG
Start
Start
Buzzer & LED Test
Battery Aging Test
Manual Battery Test
You haven't established the baseline.
Please execute Baseline build for Aging
Reference before battery aging test.
Item
Description
Buzzer & LED Test
Start the buzzer & LED test.
Battery Aging Test
Start the battery aging test. There are three situations as follows.
1. If the following screen appears, it means that you haven't est-
ablished the baseline. Please refer to
7.9.4 Battery Setting
to establish the baseline.
Battery Aging Test
You haven't established the baseline.
Please execute Baseline build for Aging
Reference before battery aging test.
2. If the following screen appears,
Battery Aging Test
Start
it means that you cannot start the battery aging test because
all of the following conditions are not matched for you to
execute the battery aging test. The conditions include that:
a. The battery status icon
illuminates green.
E 7KHEDWWHULHVDUHLQWKHÀRDWLQJFKDUJHVWDWXV
c. Battery voltage is
charging voltage setup value minus
20V.
d. Charging current is < 10A.
3. If the following screen appears, it means that you can start
the battery aging test.
Battery Aging Test
Start
(1) Once you tap the
Start
, the following screen will pop
up to ask if you want to abort aging test.
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......