6 - 4
Ultron DPM series
y
3UH7XUQRႇ:DUQLQJVIRU6LQJOH8QLW
If you perform turn-off procedures for single unit, all power will be completely cut off.
Please make sure the critical loads connected to the UPS have already been safely shut
GRZQEHIRUH\RXSHUIRUPWKHWXUQRႇSURFHGXUHV
Parallel Units
y
Pre Start-up Warnings for Parallel Units
1. You can parallel at maximum eight UPS units.
For 1000kW UPS, you can parallel at maximum 8 UPS system cabinets, and each
UPS system cabinet can connect to up to 3 power modules.
For 1250kW UPS, you can parallel at maximum 8 UPS system cabinets, and each
UPS system cabinet can connect to up to 4 power modules.
2. Make sure that all of switches and breakers, including every external battery
cabinet’s breaker (Q5), are turned to the
OFF
position.
3. With the provided parallel cable, UPSs with the same capacity, voltage, frequency
and version can be paralleled. For version information, please refer to
7.10.8
Version
. Please only use the provided parallel cable to parallel the UPS units;
otherwise, parallel functions will fail.
4. For parallel units, ensure that each parallel cable (provided) is connected well.
5. Please set up each parallel UPS’s parallel switch. Please refer to
4.1.4 Parallel
Switch
.
6. Check if the wiring is correct. Ensure that the AC power’s voltage, frequency, phase
and battery type meet the UPS’s requirements.
%HIRUHVWDUWXSRIWKHSDUDOOHOXQLWVTXDOL¿HGVHUYLFHSHUVRQQHOPXVWVHWHDFK836¶V
'
Parallel Group ID
' (1 or 2) and '
Parallel ID
' (1 ~ 8) through the LCD. Otherwise,
the parallel UPSs cannot be started. Please refer to
6.2.3 Bypass Mode Start-up
Procedures
and
7.9.6 Parallel Setting
.
8. For parallel units, ensure that every operation procedure is synchronized to all
parallel UPSs.
)RUSDUDOOHODSSOLFDWLRQLI\RXMXVWZDQWWRRSHUDWHDVSHFL¿F836EXWQRWDOOSDUDOOHO
ones, please contact service personnel.
y
3UH7XUQRႇ:DUQLQJVIRU3DUDOOHO8QLWV
,I\RXZDQWWRWXUQRႇRQHRIWKHSDUDOOHO836VSOHDVHFKHFNZKHWKHUWKHUHPDLQLQJ
parallel units’ total capacity exceeds the total critical loads. If the remaining parallel
units’ total capacity is less than the total critical loads, all parallel units will shut down
due to overload.
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......