7 - 1 3
7
LCD Display & Settings
The screen above indicates that the UPS is in
ECO
mode. The inverter is in the
ready-to-power-on status, and the power supply of the loads comes from the
bypass. For
ECO
mode settings, please refer to
7.9.2 Mode Setting
and
6.2.5 ECO
Mode Start-up Procedures
.
Bypass
Manual Bypass Mode
1
2019-Mar-01
09:30
Bypass
Load
0 %
Mains
5
UPS-1.1
10 mins
After the external maintenance bypass cabinet’s Manual Bypass breaker (Q3) is
turned on, the UPS will be switched to
Manual Bypass
mode and the screen above
will appear. Before maintenance, the UPS must be switched to this mode and you
must ensure that the external maintenance bypass cabinet’s Input Breaker (Q1),
Bypass Breaker (Q2) and external battery cabinet’s breaker (Q5) are turned
OFF
.
After that, the LCD will be off and the loads will not be protected. If there is any
sudden malfunction in the bypass source, the loads will lose power. Please refer to
6.2.4 Manual Bypass Mode Start-up Procedures
.
7.7 Main
Menu
Tap the
Main Menu
and you will see the
Main Menu
includes
Measurement
,
UPS
Setup
and
Maintenance
as shown below.
UPS-1.1
Standby
2019-Mar-01
09:30
Bypass
Load
0 %
Mains
EVENT LOG
10mins
Load
0 %
Measurement
Maintenance
UPS Setup
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......