6 - 2 0
Ultron DPM series
(b) Dual Input:
Turn
ON
the external maintenance bypass cabinet’s manual bypass breaker (Q3)
and turn
OFF
the external maintenance bypass cabinet’s bypass breaker (Q2) and
input breaker (Q1). Now, the grey inverter icon
becomes green
.
At this moment, it is manual bypass to supply power to the connected loads and
the UPS begins shutdown. About 3 ~ 5 minutes, the green inverter icon
becomes grey
and the tri-color LED indicator remains yellow.
2019-Mar-01
09:30
UPS-1.1
Bypass
Manual Bypass Mode
1
10 mins
Bypass
Load
0 %
Mains
6
Switch
OFF
each external battery cabinet’s breaker (Q5). After that, both of the
/&'DQGWKHWULFRORU/('LQGLFDWRUDUHRႇ
y
Switching from manual bypass mode to online mode
1
Switch
ON
each external battery cabinet’s breaker (Q5). At this moment, the
/&'DQGWKHWULFRORU/('LQGLFDWRUDUHERWKRႇ)RUWKHWULFRORU/('LQGLFDWRU¶V
location, please refer to
Figure 2-13
.
2
(a) Single Input:
Switch
ON
the external maintenance bypass cabinet’s input breaker (Q1) and
RXWSXWEUHDNHU41RZWKH/&'LVRQVHHWKH¿JXUHEHORZDQGWKHWULFRORU
LED indicator illuminates yellow.
(b) Dual Input:
Switch
ON
the external maintenance bypass cabinet’s bypass breaker (Q2), input
EUHDNHU4DQGRXWSXWEUHDNHU41RZWKH/&'LVRQVHHWKH¿JXUHEHORZ
and the tri-color LED indicator illuminates yellow.
Содержание Ultron DPM Series
Страница 12: ...1 6 Ultron DPM series 1 5 Standard Compliance UPS Capacity 1000kW 1250kW UL 1778...
Страница 38: ......
Страница 66: ......
Страница 232: ......
Страница 233: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 235: ...9 1 9 Maintenance Maintenance 9...
Страница 243: ...10 Troubleshooting 10 1 Troubleshooting 10...
Страница 256: ......
Страница 257: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 260: ......
Страница 261: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 264: ......